| Range |
Compact |
| Product name |
Compact NSX |
| Product or component type |
Circuit breaker |
| Device short name |
Compact NSX250B |
| Device application |
Distribution |
| Poles description |
3P |
| Protected poles description |
3t |
| Network type |
AC |
| Network frequency |
50/60 Hz |
| [In] rated current |
250 A ( 40 °C ) |
| [Ui] rated insulation voltage |
800 V AC 50/60 Hz [Uimp] rated impulse withstand voltage 8 kV |
| [Ue] rated operational voltage |
690 V AC 50/60 Hz |
| Breaking capacity code |
B (25 kA) AC |
| Breaking capacity |
25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 |
| |
15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
| |
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| |
40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
| |
|
| [Ics] rated service breaking capacity |
Ics 15 kA 500 V AC 50/60 Hz conforming to IEC 60947-2 |
| |
Ics 20 kA 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| |
Ics 25 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2 Ics |
| |
40 kA 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
| Suitability for isolation |
Yes conforming to EN 60947-2 Yes conforming to IEC 60947-2 |
| Utilisation category |
Category A |
| Trip unit name |
TM-D |
| Trip unit technology |
Thermal-magnetic |
| Trip unit protection functions |
LI |
| Trip unit rating |
250 A ( 40 °C ) |
| Protection type |
Overload protection (thermal) L |
| Short-circuit protection (magnetic) I |
|
| Pollution degree |
3 conforming to IEC 60664-1 |
| Complementary |
|
| Control type |
Toggle |
| Mounting mode |
Fixed |
| Mounting support |
Backplate |
| Upside connection |
Front |
| Downside connection |
Front |
| Mechanical durability |
20000 cycles |
| Electrical durability |
10000 cycles 440 V In conforming to IEC 60947-2 |
| |
10000 cycles 690 V In/2 conforming to IEC 60947-2 |
| |
20000 cycles 440 V In/2 conforming to IEC 60947-2 |
| |
5000 cycles 690 V In conforming to IEC 60947-2 |
| Connection pitch |
35 mm |
| Local signalling |
Positive contact indication Long time pick-up adjustment type Ir Adjustable |
| Long time pick-up adjustment range |
0.7...1 x In Long time delay adjustment type Fixed |
| [Tr] long-time delay adjustment range |
15 s 6 x Ir |
| 120...400 s 1.5 x In |
|
| Short-time pick-up adjustment type Isd |
Adjustable |
| [Isd] short-time pick-up adjustment range |
|
| 5...10 x In |
|
| Short-time delay adjustment type |
Fixed |
| Height |
161 mm |
| Width |
105 mm |
| Depth |
86 mm |
| Product weight |
2.4 kg |
| Environment |
|
| Overvoltage category |
Class II |
| Electrical shock protection class |
Class II |
| Standards |
EN/IEC 60947 |
| Product certifications |
CCC Marine EAC |
| IP degree of protection |
IP40 conforming to IEC 60529 |
| IK degree of protection |
IK07 conforming to IEC 62262 Ambient air temperature for operation -35...70 °C |
| Ambient air temperature for storage |
-55...85 °C |
| Offer Sustainability |
|
| Sustainable offer status |
Green Premium product |
| REACh |
Reference not containing SVHC above the threshold Reference not containing SVHC above the threshold |
| Product environmental profile |
Available |
| Product end of life instructions |
Available |